ElectroCalc › Voltage Drop Calculator

Voltage Drop Calculator

Enter the current, the cable and the one-way length. You get the voltage drop in volts and percent, the voltage at the load and the power lost in the cable — or the longest run, or the smallest standard cable that stays within your limit. Free, no sign-up, the same numbers as the ElectroCalc app.

Voltage drop—
Drop—
Drop, percent—
Voltage at the load—
Power lost in the cable—
Cable—
Derated cable size, breaker, fault currentPro in the app
Single-line diagram of the installationPro in the app
ElectroCalc Pro

Doing the whole installation?

The ElectroCalc app does everything on this page offline, and Pro adds the rest. One payment, no subscription.

  • Cable derating, breakers, fault current, earth loop and RCDs
  • Single-line diagram with fault level at every board
  • Unlimited projects and calculations
  • PDF reports with diagrams, your company name and logo, plus CSV
  • Compare scenarios side by side
  • No adverts anywhere

Questions

How is voltage drop calculated?

ΔV = k × I × L × (R′ cos φ + X′ sin φ), where k is 2 for single-phase and DC (the current goes out and back) and √3 for three-phase, L is the one-way length, R′ the conductor's resistance per metre at its temperature and X′ its reactance. This is the approximate method of IEC 60364-5-52 Annex G.

What voltage drop is allowed?

IEC 60364-5-52 suggests 3 % for lighting and 5 % for other uses, measured from the origin of the installation; BS 7671 uses the same figures for a public supply. The NEC's informational notes suggest 3 % for a branch circuit and 5 % for feeder and branch together. Enter the limit that applies to you.

Why does the conductor temperature matter?

Copper's resistance rises about 0.39 % for every degree. A cable running at 70 °C has about 20 % more resistance than at 20 °C, so it drops about 20 % more voltage. The calculator uses 70 °C (IEC) or 75 °C (NEC) unless you change it.

Is the cable it picks safe to use?

It is chosen for voltage drop only — check current-carrying capacity too. The ElectroCalc app does that with Pro: cable derating for grouping and ambient temperature, breaker selection, fault current and earth loop impedance.

Why is the length one way?

Because that is what you measure on site. The calculator doubles it for single-phase and DC, and uses √3 for three-phase, so do not enter the out-and-back length yourself.

How it is calculated

  • ΔV = k × I × L × (R′ cos φ + X′ sin φ): k = 2 for single-phase and DC, √3 for three-phase (line-to-line); L is the one-way length. DC ignores reactance and power factor.
  • R′ = ρ20 (1 + α (T − 20)) / A: copper 0.017241 Ω·mm²/m and 0.00393 /K (IEC 60028), aluminium 0.028264 Ω·mm²/m and 0.00403 /K (IEC 60889), from the nominal area.
  • Reactance X′ = 0.08 Ω/km, the value IEC 60364-5-52 Annex G suggests when the real figure is not known.
  • Sizes: IEC 60228 from 1 to 630 mm², or 14 AWG to 1000 kcmil with their exact areas.
  • Approximate method of IEC 60364-5-52 Annex G; resistance from conductor temperature. Length is one way.

The calculation runs in your browser; nothing you type is sent anywhere. It is the same engine as the ElectroCalc app.