Heat Pump Radiator Size Calculator
Enter the room's heat loss and the flow and return temperatures. You get the ΔT50 rating the radiator needs, how much bigger that is than a radiator sized for a gas boiler, whether the radiator you have is still big enough, and panel sizes that are. Free, no sign-up, the same numbers as the Heatwise app.
Sizing a whole house?
The Heatwise app does everything on this page offline, and Pro adds the rest. One payment, no subscription.
- Whole house room by room, with totals feeding boiler and heat pump sizing
- Heat pump size and unvented cylinder + expansion vessel
- Unlimited projects and history
- One project PDF report with your company name and logo, plus CSV
- Compare two options side by side (boiler vs heat pump, old vs new radiator)
- No adverts anywhere
Questions
Why does a radiator give less heat at a lower flow temperature?
A radiator's catalogue output is rated at ΔT50: water about 50 K warmer than the room (75/65 °C water, 20 °C room). Output falls faster than the temperature difference, as (ΔT / 50)^n with n about 1.3 for steel panels. At 50/45 °C and a 21 °C room ΔT is 26.5 K, so the radiator gives only about 44 % of its rating.
What is ΔT50?
The temperature difference at which radiator outputs are rated under EN 442: the mean water temperature minus the room temperature, 50 K. Every maker's data sheet quotes this figure, so it is the number to compare when you buy.
Arithmetic or logarithmic mean temperature difference?
The arithmetic mean, (flow + return) / 2 − room, is what most installers use. The logarithmic mean is what EN 442 is based on and gives a slightly smaller ΔT when the flow–return drop is large. For a 5 K drop the two are almost the same.
What does Part L say about flow temperature?
In England, since June 2022, a new or fully replaced wet heating system must be designed for a flow temperature of 55 °C or less. The calculator tells you whether your design meets that.
Where do the radiator sizes come from?
From generic typical outputs for steel panel radiators, with no brand named. Real models differ by about 10–15 %, so check the maker's data sheet before you order.
How do I know the room's heat loss?
The Heatwise app calculates it from the room's walls, windows, floor, roof and air changes. With Pro it does every room of the house and adds them up for the boiler or heat pump.
How it is calculated
- Mean temperature difference: ΔT = (flow + return) / 2 − room, or the logarithmic mean (flow − return) / ln((flow − room) / (return − room)).
- Output factor, EN 442: f = (ΔT / 50)^n, with n = 1.3 for steel panel radiators.
- Rating needed: Φ50 = room heat loss / f. The existing radiator gives its ΔT50 rating × f.
- Sizes: generic typical ΔT50 outputs per metre for Type 21, 22 and 33 panels at the chosen height, rounded up to the next 100 mm (400–3000 mm).
- Generic typical outputs for steel panel radiators (no brand); real models differ by ±10–15 % — check the maker's data sheet.
The calculation runs in your browser; nothing you type is sent anywhere. It is the same engine as the Heatwise app.