The short answer: find the airflow (CFM) each duct must carry, pick a design friction rate from the blower's available static pressure, size each round duct for that CFM at that friction rate, round up to the next size you can buy, then check the velocity. Example: 400 CFM at 0.1 in.wg/100 ft in metal duct needs a 10 in round duct at about 730 fpm.
The three numbers behind every duct
- Airflow (CFM or L/s) — how much air the duct must move.
- Friction rate (in.wg per 100 ft, or Pa/m) — how much pressure the air loses for each length of straight duct.
- Velocity (fpm or m/s) — how fast the air moves. Too fast is noisy; too slow wastes duct and can hurt the throw at the grille.
For a given airflow, a smaller duct means higher velocity and higher friction. Duct sizing is choosing the size where these three agree with what your blower can push.
Step 1: Find the CFM for each room
The right source is a room-by-room load calculation (in the US, ACCA Manual J). From the room's sensible load and the supply temperature difference:
Example: a bedroom with a 6,000 BTU/h sensible cooling load and a 20 °F difference between supply air and room air needs 6,000 ÷ (1.08 × 20) ≈ 280 CFM. The 1.08 factor is for standard air at sea level.
For the whole system, about 400 CFM per ton of cooling is the usual starting point (lower in humid climates, higher in dry ones). Split the system CFM between rooms in proportion to their loads. The trunk carries the sum of the branches it feeds.
Step 2: Work out the friction rate
The friction rate is not a number you guess. It comes from how much pressure the blower has left for the ductwork:
- Take the blower's rated external static pressure at your airflow (from the equipment data).
- Subtract everything that is not duct: coil, filter, supply registers, return grille, dampers.
- What remains is the available static pressure for the ducts.
- Add up the total effective length (TEL) of the longest supply run plus the longest return run: the straight lengths plus the equivalent length of every elbow, boot and take-off.
Example: the blower gives 0.50 in.wg. The coil takes 0.20, the filter 0.10 and the grilles 0.06, which leaves 0.14 in.wg. The longest supply and return together have a TEL of 175 ft. So the friction rate is 0.14 × 100 ÷ 175 = 0.08 in.wg/100 ft.
Many residential systems land between 0.06 and 0.10 in.wg/100 ft. If you get a number far outside that, check your fitting lengths and the filter, which is often the hidden loss.
Step 3: Size each round duct
With the CFM and the friction rate, each duct has one round diameter that carries that airflow at exactly that friction rate. This is the equal friction method, and it is what a slide-rule ductulator does. You then round up to the next size you can buy, which lowers both the friction and the velocity a little.
Here are some results from the Ductwise engine for galvanised steel duct with longitudinal seams, standard air:
| Airflow | Friction rate | Exact size | Use | Velocity | Actual friction |
|---|---|---|---|---|---|
| 100 CFM | 0.10 | 5.8 in | 6 in | 509 fpm | 0.083 |
| 400 CFM | 0.10 | 9.7 in | 10 in | 733 fpm | 0.085 |
| 800 CFM | 0.10 | 12.6 in | 14 in | 748 fpm | 0.059 |
| 1,200 CFM | 0.08 | 15.3 in | 16 in | 859 fpm | 0.064 |
Friction rates are in in.wg per 100 ft. Above 10 in, round duct here comes in 2 in steps, which is why 12.6 in becomes 14 in.
Metric example: 200 L/s at 0.8 Pa/m needs a 252 mm duct, so the next EN 1506 size, 280 mm, at 3.2 m/s and 0.48 Pa/m.
Step 4: Check the velocity
After rounding up, look at the velocity of the duct you will actually install:
- Common rules of thumb for homes are up to about 600–700 fpm in branches and up to about 900 fpm in trunks, to keep the noise down.
- Ductwise warns below about 400 fpm (2 m/s), where you are paying for more duct than you need and the grille throw suffers, and above about 1,770 fpm (9 m/s), where branches are usually heard.
If noise is the limit, size by velocity instead: pick the speed you want and get the diameter from that. For example, 400 CFM at 700 fpm gives 10.2 in, so a 12 in duct at about 510 fpm.
Rectangular ducts
A rectangular duct does not carry the same air as a round duct with the same area. Size the round duct first, then find the rectangle with the same friction and airflow (its "equivalent diameter"), and round the sides up to the next 2 in or 50 mm. Keep the aspect ratio low: a 4:1 duct needs much more metal than a 2:1 duct for the same job.
Flex duct
Flex duct is much rougher than metal. In the Ductwise engine, 100 CFM at 0.1 in.wg/100 ft needs 5.8 in in metal but 6.6 in in flex, so 7 in instead of 6 in. That is for flex pulled tight. Sagging or compressed flex loses much more, so pull it straight, support it well and keep the runs short.
Common mistakes
- Using a friction rate from habit (often 0.1) instead of working it out from the blower and the TEL.
- Leaving the fittings out of the length. Elbows and boots often add more equivalent length than the straight duct.
- Sizing flex as if it were metal.
- An undersized return. The return carries the same air as the supply and needs the same care.
- Rounding down to save money. Always round up to the next standard size.
Do the maths in ten seconds
The free Duct Size Calculator runs Step 3 and Step 4 in your browser, in CFM or L/s, for five duct materials.
The Ductwise app by BEK Service Ltd does the same on your phone, offline, with no account. Pro is one payment, no subscription, and adds rectangular and flat-oval ducts, fitting losses and total system pressure, airflow from heating and cooling loads, real air density for altitude and temperature, unlimited saved projects and a clean report for your client.
Questions
What size duct do I need for 400 CFM?
At a friction rate of 0.1 in.wg per 100 ft in galvanised steel, 400 CFM needs a 9.7 in round duct, so you use a 10 in duct. It runs at about 730 fpm.
What size duct do I need for 100 CFM?
At 0.1 in.wg per 100 ft in metal duct, 100 CFM needs a 5.8 in round duct, so a 6 in duct, at about 510 fpm. Flex duct usually needs one size bigger.
What friction rate should I use for duct sizing?
Work it out from the system: take the blower's external static pressure, subtract the coil, filter and grille losses, multiply by 100 and divide by the total effective length of the longest run. Many residential systems land between 0.06 and 0.10 in.wg per 100 ft.
How many CFM per ton of cooling?
About 400 CFM per ton is the usual starting point (350 in humid climates, up to 450 in dry ones). Use the equipment's own data when you have it.
Is there a free duct sizing app?
Ductwise by BEK Service Ltd is free on iPhone and Android and works offline with no account. It sizes round ducts by equal friction or velocity in CFM or L/s. Pro is a one-time purchase for rectangular ducts, fittings, site air and reports.
How the numbers on this page were made
Every duct size here comes from the Ductwise engine: the Darcy–Weisbach equation with a Colebrook–White friction factor, the roughness of the chosen duct material, and standard air (20 °C at sea level, 1.204 kg/m³). These are the relations the ASHRAE duct friction chart is drawn from. Standard round sizes are 4–10 in in 1 in steps and 12–48 in in 2 in steps, and EN 1506 in metric.
This guide explains the method. It does not replace a full design to ACCA Manual D, your local code or the equipment maker's data, and the person who designs the system is responsible for it.