Duct size chart: CFM to round duct size
These tables answer the two questions asked most on the job: what size round duct a given CFM needs, and how much air a given duct carries. Every figure was computed with the same engine as the Ductwise app and its free web calculator: standard air at 68 °F (20 °C) and sea level, the Darcy–Weisbach equation with a Colebrook–White friction factor, and the roughness of the duct material. Sizes are rounded up to the app's standard imperial list (4 to 10 in by the inch, then even sizes to 48 in).
How to read the chart
Pick the friction rate your design uses, find your airflow in the left column, and read the standard round duct size. The exact diameter is shown too: when it sits just above a standard size, such as 10.1 in for 400 CFM at 0.08, rounding up to 12 in is the safe answer, and a 10 in duct would run a little above the target friction. The velocity is the speed of the air in the standard duct, in feet per minute.
The app and the web calculator flag a duct whose air is below about 400 FPM (poor throw) or above about 1,770 FPM (9 m/s, likely to be heard).
CFM to round duct size, galvanised steel
| Airflow (CFM) | At 0.06 in.wg/100 ft | At 0.08 in.wg/100 ft | At 0.10 in.wg/100 ft |
|---|---|---|---|
| 50 | 5 in (exact 4.96 in, 367 FPM) | 5 in (exact 4.68 in, 367 FPM) | 5 in (exact 4.47 in, 367 FPM) |
| 75 | 6 in (exact 5.77 in, 382 FPM) | 6 in (exact 5.44 in, 382 FPM) | 6 in (exact 5.19 in, 382 FPM) |
| 100 | 7 in (exact 6.42 in, 374 FPM) | 7 in (exact 6.05 in, 374 FPM) | 6 in (exact 5.78 in, 509 FPM) |
| 125 | 7 in (exact 6.97 in, 468 FPM) | 7 in (exact 6.57 in, 468 FPM) | 7 in (exact 6.27 in, 468 FPM) |
| 150 | 8 in (exact 7.46 in, 430 FPM) | 8 in (exact 7.03 in, 430 FPM) | 7 in (exact 6.72 in, 561 FPM) |
| 200 | 9 in (exact 8.30 in, 453 FPM) | 8 in (exact 7.82 in, 573 FPM) | 8 in (exact 7.47 in, 573 FPM) |
| 250 | 10 in (exact 9.02 in, 458 FPM) | 9 in (exact 8.50 in, 566 FPM) | 9 in (exact 8.12 in, 566 FPM) |
| 300 | 10 in (exact 9.66 in, 550 FPM) | 10 in (exact 9.10 in, 550 FPM) | 9 in (exact 8.70 in, 679 FPM) |
| 350 | 12 in (exact 10.23 in, 446 FPM) | 10 in (exact 9.64 in, 642 FPM) | 10 in (exact 9.21 in, 642 FPM) |
| 400 | 12 in (exact 10.75 in, 509 FPM) | 12 in (exact 10.14 in, 509 FPM) | 10 in (exact 9.68 in, 733 FPM) |
| 500 | 12 in (exact 11.69 in, 637 FPM) | 12 in (exact 11.02 in, 637 FPM) | 12 in (exact 10.53 in, 637 FPM) |
| 600 | 14 in (exact 12.51 in, 561 FPM) | 12 in (exact 11.80 in, 764 FPM) | 12 in (exact 11.27 in, 764 FPM) |
| 700 | 14 in (exact 13.26 in, 655 FPM) | 14 in (exact 12.50 in, 655 FPM) | 12 in (exact 11.94 in, 891 FPM) |
| 800 | 14 in (exact 13.94 in, 748 FPM) | 14 in (exact 13.14 in, 748 FPM) | 14 in (exact 12.56 in, 748 FPM) |
| 1000 | 16 in (exact 15.15 in, 716 FPM) | 16 in (exact 14.29 in, 716 FPM) | 14 in (exact 13.65 in, 935 FPM) |
| 1200 | 18 in (exact 16.23 in, 679 FPM) | 16 in (exact 15.30 in, 859 FPM) | 16 in (exact 14.62 in, 859 FPM) |
| 1400 | 18 in (exact 17.20 in, 792 FPM) | 18 in (exact 16.22 in, 792 FPM) | 16 in (exact 15.50 in, 1003 FPM) |
| 1600 | 20 in (exact 18.08 in, 733 FPM) | 18 in (exact 17.05 in, 905 FPM) | 18 in (exact 16.30 in, 905 FPM) |
| 2000 | 20 in (exact 19.66 in, 917 FPM) | 20 in (exact 18.55 in, 917 FPM) | 18 in (exact 17.73 in, 1132 FPM) |
How much air a round duct carries
The airflow at which each duct size reaches the friction rate shown. Flexible duct is modelled fully stretched, with 3.0 mm (0.12 in) roughness; flex that sags, bends or is compressed carries noticeably less, which Manual D treats separately and this table does not.
| Round duct | Galvanised at 0.08 | Galvanised at 0.10 | Flexible (stretched) at 0.08 |
|---|---|---|---|
| 4 in | 33 CFM (375 FPM) | 37 CFM (425 FPM) | 23 CFM (267 FPM) |
| 5 in | 60 CFM (439 FPM) | 68 CFM (497 FPM) | 43 CFM (313 FPM) |
| 6 in | 98 CFM (499 FPM) | 111 CFM (564 FPM) | 70 CFM (357 FPM) |
| 7 in | 148 CFM (555 FPM) | 168 CFM (628 FPM) | 106 CFM (397 FPM) |
| 8 in | 212 CFM (608 FPM) | 240 CFM (687 FPM) | 152 CFM (436 FPM) |
| 9 in | 291 CFM (659 FPM) | 329 CFM (744 FPM) | 209 CFM (473 FPM) |
| 10 in | 386 CFM (707 FPM) | 436 CFM (799 FPM) | 277 CFM (508 FPM) |
| 12 in | 628 CFM (799 FPM) | 709 CFM (903 FPM) | 452 CFM (576 FPM) |
| 14 in | 947 CFM (886 FPM) | 1069 CFM (1000 FPM) | 683 CFM (639 FPM) |
| 16 in | 1351 CFM (968 FPM) | 1524 CFM (1091 FPM) | 975 CFM (698 FPM) |
| 18 in | 1847 CFM (1045 FPM) | 2083 CFM (1179 FPM) | 1335 CFM (755 FPM) |
| 20 in | 2443 CFM (1120 FPM) | 2754 CFM (1263 FPM) | 1767 CFM (810 FPM) |
Worked example: a 3-ton system
- A 3-ton system at about 400 CFM per ton moves about 1,200 CFM. Check the blower's real airflow from the equipment data.
- From Manual D, the available static pressure and the total effective length of the longest run give the design friction rate. Say it comes to 0.08 in.wg per 100 ft.
- Trunk: 1,200 CFM at 0.08 needs 15.3 in exactly, so a 16 in round trunk, running at about 859 FPM and 0.064 in.wg per 100 ft.
- A bedroom branch at 150 CFM needs 7.0 in exactly, so an 8 in branch at about 430 FPM.
- A 400 CFM section needs 10.1 in exactly: 12 in at 509 FPM, or 10 in if you accept a little more friction.
The Ductwise app does steps 3 to 5 for every duct in seconds, and with Pro converts the round trunk to a rectangular one that fits the joist bay.
Where ACCA Manual D, IRC M1601.1 and IECC R403.3 come in
In the US, IRC section M1601.1 and IECC section R403.3 (its duct design subsection in the 2024 edition) point to ACCA Manual D for sizing residential duct systems. Manual D (ANSI/ACCA 1 Manual D) matches the duct system's resistance to the blower: the design friction rate is the available static pressure times 100, divided by the total effective length of the longest run, including the equivalent lengths of its fittings.
The sizing in this chart and in the Ductwise app is based on Manual D methods: once you have the design friction rate, each duct is sized to it by equal friction. Neither calculates available static pressure or total effective length, and neither does a Manual J load calculation; those steps stay in your Manual D design.
Assumptions and limits
- Standard air: 68 °F (20 °C) at sea level, 1.204 kg/m³ (0.075 lb/ft³). At altitude or at other temperatures air is lighter or heavier; the Ductwise app with Pro corrects for both.
- Galvanised steel with longitudinal seams, 0.09 mm (0.0003 ft) roughness. Smoother or rougher materials change the result; the app and the web calculator offer five materials.
- Straight duct only. Elbows, tees, boots and grilles add pressure loss on top; with Pro the app adds fitting losses from their loss coefficients.
- Round duct only. A rectangular duct of the same area carries less air at the same friction rate; use an equivalent-diameter conversion, not the area.
Sources
- ACCA: Manual D, Residential Duct Systems (ANSI/ACCA 1 Manual D) (read 2026-11-23)
- International Code Council: 2021 International Residential Code, Chapter 16 Duct Systems (M1601.1) (section M1601.1, 2026-11-23)
- International Code Council: proposal REC2D-3-23, ANSI/ACCA Manual D reference for IECC R403.3.1 Duct system design (2024 IECC, read 2026-11-23)
- Green Building Advisor: HVAC design requirements in the international building codes (quotes M1601.1, read 2026-11-23)
- ASHRAE Handbook, Fundamentals: Chapter 21, Duct Design (friction chart method, Colebrook equation)
Figures are computed by the Ductwise engine as a sizing aid. They are not a substitute for a Manual D design or for the judgement of a qualified designer. ACCA and Manual D are trademarks of the Air Conditioning Contractors of America; Ductwise and BEK Service LTD are not affiliated with or endorsed by ACCA or the International Code Council.