Ductwise › Duct Pressure Loss Calculator

Duct Pressure Loss Calculator

Enter the airflow, the diameter of a round duct and the length of the run. You get the pressure the straight run loses, how fast the air moves, its velocity pressure and the friction rate. Free, no sign-up, the same numbers as the Ductwise app.

Straight-run pressure loss—
Velocity—
Velocity pressure—
Friction rate—
Reynolds number—
Friction factor (Darcy)—
Cross-section area—
Outside surface area of the run—
Fitting losses and total system pressurePro in the app
Rectangular and flat-oval ductsPro in the app
Ductwise Pro

Need fittings, or a rectangular duct?

The Ductwise app does everything on this page offline, and Pro adds the rest.

  • Rectangular and flat-oval ducts
  • Fitting losses and total system pressure
  • Airflow from heating and cooling loads
  • Real air density — altitude and temperature
  • Unlimited saved projects
  • Share a clean report with your client
  • No ads, ever

Questions

How is duct pressure loss calculated?

With the Darcy–Weisbach equation: the friction factor, divided by the diameter, times the velocity pressure, gives the loss per metre; times the length gives the loss of the run. The friction factor comes from the Colebrook–White equation and the roughness of the duct material you choose.

Does this include bends, tees and other fittings?

No. This page gives the straight-run friction loss. The Ductwise app with Pro adds fitting losses from their loss coefficients and the total system pressure.

What is velocity pressure?

The pressure equivalent of the air's speed, ½ρv². Fitting losses are quoted as a multiple of it, so it is the number you need next when you add bends and tees.

Which air density does the calculator use?

Standard air: 20 °C at sea level, 1.204 kg/m³. The Ductwise app with Pro corrects the density for your site's altitude and air temperature.

Can I check a rectangular duct?

The Ductwise app does: with Pro it analyses rectangular and flat-oval ducts as well as round ones.

How it is calculated

  • Air: ASHRAE standard air, 20 °C at 101.325 kPa (1.204 kg/m³), viscosity from Sutherland's law.
  • Velocity from the duct's actual free area; velocity pressure ½ρv².
  • Friction: Darcy–Weisbach with the Colebrook–White friction factor, solved by Newton iteration (64/Re below Re 2,300).
  • Straight-run loss: the friction rate times the length. Fittings are not included.
  • Surface area: the duct's circumference times the length, for insulation or sheet-metal take-off.

The calculation runs in your browser; nothing you type is sent anywhere. It is the same engine as the Ductwise app.